EG4 6000XP with Basen 48V 200Ah

Home / Comparisons / EG4 6000XP with Basen 48V 200Ah
Pair check
Unverified: Partial match, some fields unverified.

Checked as a single pack, which covers this inverter’s charge current on its own.

Full specifications: EG4 6000XP and Basen 48V 200Ah.

The four checks

Voltage window: Overlapping window 44.8 to 58.4 V

The inverter operates from 40 to 60 volts and the battery cuts off outside 44.8 to 58.4 volts. Both stay inside 44.8 to 58.4 volts, which covers a normal LiFePO4 charge and discharge cycle with margin at both ends.

Match

Charge current: 120 A into a 200 A limit

The inverter tops out at 120 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Match

Surge rating: Battery surge figure unpublished

A surge to 12000 watts draws roughly 250 amps at 48 volts. This battery publishes a 200 amp continuous rating and no separate surge figure, and continuous is the wrong number to check a motor start against. Confirm the peak rating and its duration with the manufacturer before running motor loads.

Unverified

Closed-loop communication: Both speak CAN, RS485, no document names the pair

The inverter and the battery both support CAN, RS485. Neither manufacturer publishes a document naming the other unit, and a shared bus standard is not a shared message format. It may well work on the bench. Confirm the protocol setting with both manufacturers before relying on BMS control.

Unverified

What this means when you install it

Set the inverter charge current to 120 amps or less. That is the inverter maximum, which this bank can absorb. Protect the battery run with a 175 amp Class T fuse and 2/0 AWG cable.

The inverter and the battery both support CAN, RS485. Neither manufacturer publishes a document naming the other unit, and a shared bus standard is not a shared message format. It may well work on the bench. Confirm the protocol setting with both manufacturers before relying on BMS control.

Figures side by side

FieldEG4 6000XPBasen 48V 200Ah
Voltage window40 to 60 V44.8 to 58.4 V
Charge current120 A delivered200 A accepted
Peak draw12,000 W surgesurge unpublished
Usable capacityn/a10.24 kWh
CommsCAN, RS485CAN, RS485
Inverter source status: Read from datasheet   Battery source status: Provisional figure   Confirm every figure against the document revision shipped with your unit before commissioning.

Manufacturer documents

Manufacturer documents: EG4 product and document library. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Basen has no public document library this site has been able to verify. Every figure on this page therefore needs checking against the paperwork that shipped with your unit.

Both units, current pricing

Prices on these move week to week, and the battery is usually the line item worth watching.

EG4 6000XP on AmazonBasen 48V 200Ah on AmazonComms cable

Affiliate links. As an Amazon Associate this site earns from qualifying purchases, at no extra cost to you. Prices and stock change often, and a listing appearing here is not a statement that the pairing above is approved.

Other pairings for the Basen 48V 200Ah

Questions people actually ask

Will the EG4 6000XP work with the Basen 48V 200Ah?

Partial match, some fields unverified. Checked as a single pack, which covers this inverter’s charge current on its own. The four checks below show which field produced that result.

What does this pairing cost to wire up?

Beyond the two units, a 175 amp Class T fuse and holder, 2/0 AWG battery cable cut to matched lengths, and a busbar if you are running 1 packs. A comms cable if you intend to attempt closed loop, and the pinout is rarely the same between brands.

Where does this pairing go wrong in practice?

The inverter and the battery both support CAN, RS485. Neither manufacturer publishes a document naming the other unit, and a shared bus standard is not a shared message format. It may well work on the bench. Confirm the protocol setting with both manufacturers before relying on BMS control.

What charge current should I set?

The inverter tops out at 120 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Field notes on this kind of problem