Sol-Ark 30K-3P with Redodo 48V 100Ah

Home / Comparisons / Sol-Ark 30K-3P with Redodo 48V 100Ah
Pair check
Conflict: Specs conflict on at least one field.

Checked as a bank of 2 packs, which is the smallest number that accepts this inverter’s 100 amp charge current. Fewer packs still run the system, with the charge rate capped in inverter settings.

Full specifications: Sol-Ark 30K-3P and Redodo 48V 100Ah.

The four checks

Voltage window: No usable overlap

The inverter window of 150 to 950 volts and the battery window of 40 to 58.4 volts do not overlap usefully. One unit reaches its limit while the other is still in normal operation.

Conflict

Charge current: 100 A into a 100 A limit

The inverter tops out at 100 amps and the battery accepts 100 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Match

Surge rating: Battery surge figure unpublished

A surge to 45000 watts draws roughly 938 amps at 48 volts. This battery publishes a 200 amp continuous rating and no separate surge figure, and continuous is the wrong number to check a motor start against. Confirm the peak rating and its duration with the manufacturer before running motor loads.

Unverified

Closed-loop communication: Battery publishes no protocol

The inverter speaks CAN, RS485. This battery publishes no communication protocol, so closed loop is not on the table and the pairing runs on voltage limits set by hand. Confirm with the manufacturer that no port exists before assuming it.

Unverified

What this means when you install it

Set the inverter charge current to 100 amps or less. That is the inverter maximum, which this bank can absorb. Protect the battery run with a 500 amp Class T fuse and two parallel runs of 4/0 cable wired to a busbar rather than daisy chained, so all 2 packs share current evenly.

The inverter speaks CAN, RS485. This battery publishes no communication protocol, so closed loop is not on the table and the pairing runs on voltage limits set by hand. Confirm with the manufacturer that no port exists before assuming it.

Figures side by side

FieldSol-Ark 30K-3PRedodo 48V 100Ah
Voltage window150 to 950 V40.0 to 58.4 V
Charge current100 A delivered100 A accepted (2 packs)
Peak draw45,000 W surgesurge unpublished
Usable capacityn/a10.24 kWh (2 packs)
CommsCAN, RS485none
Inverter source status: Provisional figure   Battery source status: Provisional figure   Confirm every figure against the document revision shipped with your unit before commissioning.

Manufacturer documents

Manufacturer documents: Sol-Ark resources and manuals. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Manufacturer documents: Redodo product pages. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Both units, current pricing

Prices on these move week to week, and the battery is usually the line item worth watching.

Sol-Ark 30K-3P on AmazonRedodo 48V 100Ah on AmazonComms cable

Affiliate links. As an Amazon Associate this site earns from qualifying purchases, at no extra cost to you. Prices and stock change often, and a listing appearing here is not a statement that the pairing above is approved.

Other pairings for the Redodo 48V 100Ah

Questions people actually ask

Will the Sol-Ark 30K-3P work with the Redodo 48V 100Ah?

Specs conflict on at least one field. Checked as a bank of 2 packs, which is the smallest number that accepts this inverter’s 100 amp charge current. Fewer packs still run the system, with the charge rate capped in inverter settings. The four checks below show which field produced that result.

What does this pairing cost to wire up?

Beyond the two units, a 500 amp Class T fuse and holder, two parallel runs of 4/0 battery cable cut to matched lengths, and a busbar if you are running 2 packs. A comms cable if you intend to attempt closed loop, and the pinout is rarely the same between brands.

Where does this pairing go wrong in practice?

The inverter speaks CAN, RS485. This battery publishes no communication protocol, so closed loop is not on the table and the pairing runs on voltage limits set by hand. Confirm with the manufacturer that no port exists before assuming it.

What charge current should I set?

The inverter tops out at 100 amps and the battery accepts 100 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Field notes on this kind of problem