Sunsynk 5kW Hybrid with SOK 48V 200Ah

Home / Comparisons / Sunsynk 5kW Hybrid with SOK 48V 200Ah
Pair check
Unverified: Partial match, some fields unverified.

Checked as a single pack, which covers this inverter’s charge current on its own.

Full specifications: Sunsynk 5kW Hybrid and SOK 48V 200Ah.

The four checks

Voltage window: Overlapping window 46.4 to 56 V

The inverter operates from 40 to 60 volts and the battery cuts off outside 46.4 to 56 volts. Both stay inside 46.4 to 56 volts, which covers a normal LiFePO4 charge and discharge cycle with margin at both ends.

Match

Charge current: 120 A into a 200 A limit

The inverter tops out at 120 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Match

Surge rating: 400 A surge for 3 s against a 208 A peak

The inverter surges to 10000 watts, about 208 amps at 48 volts, and the battery is rated for 400 amps for 3 s. A compressor or well pump start has room inside that rating. Compare the durations as well as the amps, because the ratings are only equivalent if the pack can hold its figure as long as the inverter holds its own.

Match

Closed-loop communication: Both speak CAN, RS485, no document names the pair

The inverter and the battery both support CAN, RS485. Neither manufacturer publishes a document naming the other unit, and a shared bus standard is not a shared message format. It may well work on the bench. Confirm the protocol setting with both manufacturers before relying on BMS control.

Unverified

What this means when you install it

Set the inverter charge current to 120 amps or less. That is the inverter maximum, which this bank can absorb. Protect the battery run with a 150 amp Class T fuse and 1 AWG cable.

The inverter and the battery both support CAN, RS485. Neither manufacturer publishes a document naming the other unit, and a shared bus standard is not a shared message format. It may well work on the bench. Confirm the protocol setting with both manufacturers before relying on BMS control.

Figures side by side

FieldSunsynk 5kW HybridSOK 48V 200Ah
Voltage window40 to 60 V46.4 to 56.0 V
Charge current120 A delivered200 A accepted
Peak draw10,000 W surge400 A surge
Usable capacityn/a10.24 kWh
CommsCAN, RS485CAN, RS485
Inverter source status: Provisional figure   Battery source status: Provisional figure   Confirm every figure against the document revision shipped with your unit before commissioning.

Manufacturer documents

Manufacturer documents: Sunsynk product documentation. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Manufacturer documents: SOK product documentation. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Both units, current pricing

Prices on these move week to week, and the battery is usually the line item worth watching.

Sunsynk 5kW Hybrid on AmazonSOK 48V 200Ah on AmazonComms cable

Affiliate links. As an Amazon Associate this site earns from qualifying purchases, at no extra cost to you. Prices and stock change often, and a listing appearing here is not a statement that the pairing above is approved.

Other pairings for the SOK 48V 200Ah

Questions people actually ask

Will the Sunsynk 5kW Hybrid work with the SOK 48V 200Ah?

Partial match, some fields unverified. Checked as a single pack, which covers this inverter’s charge current on its own. The four checks below show which field produced that result.

What does this pairing cost to wire up?

Beyond the two units, a 150 amp Class T fuse and holder, 1 AWG battery cable cut to matched lengths, and a busbar if you are running 1 packs. A comms cable if you intend to attempt closed loop, and the pinout is rarely the same between brands.

Where does this pairing go wrong in practice?

The inverter and the battery both support CAN, RS485. Neither manufacturer publishes a document naming the other unit, and a shared bus standard is not a shared message format. It may well work on the bench. Confirm the protocol setting with both manufacturers before relying on BMS control.

What charge current should I set?

The inverter tops out at 120 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Field notes on this kind of problem