Victron MultiPlus-II 48/5000 with Freedom Won eTower 5

Home / Comparisons / Victron MultiPlus-II 48/5000 with Freedom Won eTower 5
Pair check
Unverified: Partial match, some fields unverified.

Checked as a single pack, which covers this inverter’s charge current on its own.

Full specifications: Victron MultiPlus-II 48/5000 and Freedom Won eTower 5.

The four checks

Voltage window: Overlapping window 44 to 57.6 V

The inverter operates from 38 to 66 volts and the battery cuts off outside 44 to 57.6 volts. Both stay inside 44 to 57.6 volts, which covers a normal LiFePO4 charge and discharge cycle with margin at both ends.

Match

Charge current: 70 A into a 100 A limit

The inverter tops out at 70 amps and the battery accepts 100 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Match

Surge rating: Battery surge figure unpublished

A surge to 9000 watts draws roughly 188 amps at 48 volts. This battery publishes a 100 amp continuous rating and no separate surge figure, and continuous is the wrong number to check a motor start against. Confirm the peak rating and its duration with the manufacturer before running motor loads.

Unverified

Closed-loop communication: Named in a manufacturer document

A manufacturer document names this exact pairing for closed-loop operation over CAN. That is the only evidence this site accepts for a match on this check. Select the matching protocol profile in the inverter menu during commissioning.

Match

What this means when you install it

Set the inverter charge current to 70 amps or less. That is the inverter maximum, which this bank can absorb. Protect the battery run with a 125 amp Class T fuse and 2 AWG cable.

A manufacturer document names this exact pairing for closed-loop operation over CAN. That is the only evidence this site accepts for a match on this check. Select the matching protocol profile in the inverter menu during commissioning.

Figures side by side

FieldVictron MultiPlus-II 48/5000Freedom Won eTower 5
Voltage window38 to 66 V44.0 to 57.6 V
Charge current70 A delivered100 A accepted
Peak draw9,000 W surgesurge unpublished
Usable capacityn/a5.0 kWh
CommsVE.Bus, CANCAN
Inverter source status: Read from datasheet   Battery source status: Provisional figure   Confirm every figure against the document revision shipped with your unit before commissioning.

Manufacturer documents

Manufacturer documents: Victron manuals and datasheets. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Manufacturer documents: Freedom Won product documentation. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.

Both units, current pricing

Prices on these move week to week, and the battery is usually the line item worth watching.

Victron MultiPlus-II 48/5000 on AmazonFreedom Won eTower 5 on AmazonComms cable

Affiliate links. As an Amazon Associate this site earns from qualifying purchases, at no extra cost to you. Prices and stock change often, and a listing appearing here is not a statement that the pairing above is approved.

Other pairings for the Freedom Won eTower 5

Questions people actually ask

Will the Victron MultiPlus-II 48/5000 work with the Freedom Won eTower 5?

Partial match, some fields unverified. Checked as a single pack, which covers this inverter’s charge current on its own. The four checks below show which field produced that result.

What does this pairing cost to wire up?

Beyond the two units, a 125 amp Class T fuse and holder, 2 AWG battery cable cut to matched lengths, and a busbar if you are running 1 packs. A comms cable if you intend to attempt closed loop, and the pinout is rarely the same between brands.

Where does this pairing go wrong in practice?

A manufacturer document names this exact pairing for closed-loop operation over CAN. That is the only evidence this site accepts for a match on this check. Select the matching protocol profile in the inverter menu during commissioning.

What charge current should I set?

The inverter tops out at 70 amps and the battery accepts 100 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.

Field notes on this kind of problem