Checked as a bank of 4 packs, which is the smallest number that accepts this inverter’s 200 amp charge current. Fewer packs still run the system, with the charge rate capped in inverter settings.
Full specifications: Victron Quattro 48/15000 and ECO-WORTHY 48V 100Ah.
The four checks
Voltage window: Overlapping window 40 to 58.4 V
The inverter operates from 38 to 66 volts and the battery cuts off outside 40 to 58.4 volts. Both stay inside 40 to 58.4 volts, which covers a normal LiFePO4 charge and discharge cycle with margin at both ends.
Charge current: 200 A into a 200 A limit
The inverter tops out at 200 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.
Surge rating: Battery surge figure unpublished
A surge to 25000 watts draws roughly 521 amps at 48 volts. This battery publishes a 400 amp continuous rating and no separate surge figure, and continuous is the wrong number to check a motor start against. Confirm the peak rating and its duration with the manufacturer before running motor loads.
Closed-loop communication: Battery publishes no protocol
The inverter speaks VE.Bus, CAN. This battery publishes no communication protocol, so closed loop is not on the table and the pairing runs on voltage limits set by hand. Confirm with the manufacturer that no port exists before assuming it.
What this means when you install it
Set the inverter charge current to 200 amps or less. That is the inverter maximum, which this bank can absorb. Protect the battery run with a 350 amp Class T fuse and two parallel runs of 2/0 cable wired to a busbar rather than daisy chained, so all 4 packs share current evenly.
The inverter speaks VE.Bus, CAN. This battery publishes no communication protocol, so closed loop is not on the table and the pairing runs on voltage limits set by hand. Confirm with the manufacturer that no port exists before assuming it.
Figures side by side
| Field | Victron Quattro 48/15000 | ECO-WORTHY 48V 100Ah |
|---|---|---|
| Voltage window | 38 to 66 V | 40.0 to 58.4 V |
| Charge current | 200 A delivered | 200 A accepted (4 packs) |
| Peak draw | 25,000 W surge | surge unpublished |
| Usable capacity | n/a | 20.48 kWh (4 packs) |
| Comms | VE.Bus, CAN | none |
Manufacturer documents
Manufacturer documents: Victron manuals and datasheets. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.
Manufacturer documents: ECO-WORTHY product pages. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.
Both units, current pricing
Prices on these move week to week, and the battery is usually the line item worth watching.
Victron Quattro 48/15000 on AmazonECO-WORTHY 48V 100Ah on AmazonComms cableAffiliate links. As an Amazon Associate this site earns from qualifying purchases, at no extra cost to you. Prices and stock change often, and a listing appearing here is not a statement that the pairing above is approved.
Other pairings for the ECO-WORTHY 48V 100Ah
EG4 6000XP with ECO-WORTHY 48V 100Ah
Partial match, some fields unverified.
EG4 18KPV with ECO-WORTHY 48V 100Ah
Specs conflict on at least one field.
EG4 FlexBoss21 with ECO-WORTHY 48V 100Ah
Specs conflict on at least one field.
Sol-Ark 12K with ECO-WORTHY 48V 100Ah
Partial match, some fields unverified.
Questions people actually ask
Will the Victron Quattro 48/15000 work with the ECO-WORTHY 48V 100Ah?
Partial match, some fields unverified. Checked as a bank of 4 packs, which is the smallest number that accepts this inverter’s 200 amp charge current. Fewer packs still run the system, with the charge rate capped in inverter settings. The four checks below show which field produced that result.
What does this pairing cost to wire up?
Beyond the two units, a 350 amp Class T fuse and holder, two parallel runs of 2/0 battery cable cut to matched lengths, and a busbar if you are running 4 packs. A comms cable if you intend to attempt closed loop, and the pinout is rarely the same between brands.
Where does this pairing go wrong in practice?
The inverter speaks VE.Bus, CAN. This battery publishes no communication protocol, so closed loop is not on the table and the pairing runs on voltage limits set by hand. Confirm with the manufacturer that no port exists before assuming it.
What charge current should I set?
The inverter tops out at 200 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.