Checked as a bank of 2 packs, which is the smallest number that accepts this inverter’s 140 amp charge current. Fewer packs still run the system, with the charge rate capped in inverter settings.
Full specifications: Victron Quattro 48/10000 and Pylontech US5000.
The four checks
Voltage window: Overlapping window 44.5 to 54 V
The inverter operates from 38 to 66 volts and the battery cuts off outside 44.5 to 54 volts. Both stay inside 44.5 to 54 volts, which covers a normal LiFePO4 charge and discharge cycle with margin at both ends.
Charge current: 140 A into a 200 A limit
The inverter tops out at 140 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.
Surge rating: Battery surge figure unpublished
A surge to 20000 watts draws roughly 417 amps at 48 volts. This battery publishes a 200 amp continuous rating and no separate surge figure, and continuous is the wrong number to check a motor start against. Confirm the peak rating and its duration with the manufacturer before running motor loads.
Closed-loop communication: Named in a manufacturer document
A manufacturer document names this exact pairing for closed-loop operation over CAN. That is the only evidence this site accepts for a match on this check. Select the matching protocol profile in the inverter menu during commissioning.
What this means when you install it
Set the inverter charge current to 140 amps or less. That is the inverter maximum, which this bank can absorb. Protect the battery run with a 250 amp Class T fuse and 4/0 AWG cable wired to a busbar rather than daisy chained, so all 2 packs share current evenly.
A manufacturer document names this exact pairing for closed-loop operation over CAN. That is the only evidence this site accepts for a match on this check. Select the matching protocol profile in the inverter menu during commissioning.
Figures side by side
| Field | Victron Quattro 48/10000 | Pylontech US5000 |
|---|---|---|
| Voltage window | 38 to 66 V | 44.5 to 54.0 V |
| Charge current | 140 A delivered | 200 A accepted (2 packs) |
| Peak draw | 20,000 W surge | surge unpublished |
| Usable capacity | n/a | 9.6 kWh (2 packs) |
| Comms | VE.Bus, CAN | CAN, RS485 |
Manufacturer documents
Manufacturer documents: Victron manuals and datasheets. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.
Manufacturer documents: Pylontech product documentation. Figures here should be read against the revision that covers your serial number, because manufacturers revise specifications without changing the model name.
Both units, current pricing
Prices on these move week to week, and the battery is usually the line item worth watching.
Victron Quattro 48/10000 on AmazonPylontech US5000 on AmazonComms cableAffiliate links. As an Amazon Associate this site earns from qualifying purchases, at no extra cost to you. Prices and stock change often, and a listing appearing here is not a statement that the pairing above is approved.
Other pairings for the Pylontech US5000
EG4 6000XP with Pylontech US5000
Partial match, some fields unverified.
EG4 18KPV with Pylontech US5000
Partial match, some fields unverified.
EG4 FlexBoss21 with Pylontech US5000
Partial match, some fields unverified.
Sol-Ark 12K with Pylontech US5000
Partial match, some fields unverified.
Questions people actually ask
Will the Victron Quattro 48/10000 work with the Pylontech US5000?
Partial match, some fields unverified. Checked as a bank of 2 packs, which is the smallest number that accepts this inverter’s 140 amp charge current. Fewer packs still run the system, with the charge rate capped in inverter settings. The four checks below show which field produced that result.
What does this pairing cost to wire up?
Beyond the two units, a 250 amp Class T fuse and holder, 4/0 AWG battery cable cut to matched lengths, and a busbar if you are running 2 packs. A comms cable if you intend to attempt closed loop, and the pinout is rarely the same between brands.
Where does this pairing go wrong in practice?
A manufacturer document names this exact pairing for closed-loop operation over CAN. That is the only evidence this site accepts for a match on this check. Select the matching protocol profile in the inverter menu during commissioning.
What charge current should I set?
The inverter tops out at 140 amps and the battery accepts 200 amps, so a default install cannot overrun the pack. Adding batteries in parallel raises the accepted current further.